Manual change of T&A mode on ID0 terminal does not work

Description:
I have PR402 controller to which two PRT12 readers are connected: ID0 and ID1. After programming function [57]: "Set Predefined T&A mode (momentary)" on F1 and F2 function keys - and assigning [T&A - Entrance] and [T&A - Exit] to each key - change of the mode is possible on both terminals but proper [Entrance] and [Exit] mode is recorded only on ID1 terminal. On ID0 terminal there is only default T&A mode event recorded. What is the cause?

Solution:

The cause of the problem is that dynamic change of T&A mode is possible on ID1 terminal only. In order to control T&A mode using function keys of ID0 terminal it is necessary to enable T&A mode multiplication from ID1 terminal. To do this enable option Term.ID0 follows T&A mode of term.ID1 in Controller properties > Options.

unia flaga
Save
Cookies user preferences
We use cookies to ensure you to get the best experience on our website. If you decline the use of cookies, this website may not function as expected.
Accept all
Decline all
Read more
Essential
Essential cookies
These cookies are necessary for the correct operation of the website and therefore cannot be disabled on this level; the use of these cookies does not involve the processing of personal data. While you can disable them via your browser settings, doing so may prevent the website from working normally.
Accept
Marketing
These cookies are designed to track the users' web traffic and display advertisements that may be of interest to some users. Cookies may come from third parties and be used by them to profile your preferences. Their operation is subject to the user's consent.
Facebook
Accept
Decline
Analytical cookies
These cookies are particularly intended to enable the website administrator to monitor the website traffic statistics, as well as the sources of traffic. Such data is typically collected anonymously.
Google Analytics
Accept
Decline